PLA 5.00 issue - Cimview/PLA crashes when the user selects a set-point to change, enters any valid value for it, then hit Execute button immediately followed by the Cancel button

Instructions to copy the following screen files.

PL_AlarmLimits.cim
PL_AnalogControl.cim
PL_AnalogForce.cim
PL_DigitalControl.cim
PL_DigitalForce.cim
PL_RaiseLowerControl.cim
PL_VarIncControl.cim

Stop all the remote viewers and both primary and secondary servers. 
Close all PLA and Cimplicity related applications.


In Server system:

Copy this screens in <PROJECT>\Screens\Library folder. Do take a backup of existing screens before you copy them. (No need to copy in Secondary system project folder. When user does Project Configuration Updated, the newly copied screens will be copied in to secondary system project folder automatically)


In a redundant system:

Copy this screens in both primary, Secondary systems at "C:\Program Files\Proficy\Proficy CIMPLICITY\PACT\PROJECTS\Template\screens\Library" folder. So that any new project created using PACT will have this fix.


In all remote viewer's systems:

Copy this screens in "C:\Program Files\Proficy\Proficy CIMPLICITY\screens\Library folder


NOTE: In future if customer creates the project using SAMPLE project, after creating the project they have to copy this screens in <PROJECT>\Screens\Library folder